Residual Current Circuit Breaker With Over Current Protection

Meba rcbo circuit breaker MBR3410C

General

1.1Function
Personnel and fire protection
Cable and line protection against overload and short-circuits.

1.2 Selection
I∆n ≤ 30 mA: additional protection
In the case of direct contact.
I∆n ≤ 300 mA: preventative fire protection
In the case of ground fault currents.
AC class – Tripping is ensured for sinusoidal,
Alternating currents, whether they be quickly applied or slowly increase.

1.3 Performance & Usage
Circuit breaker is mainly suitable for overload and short protection. It is especially used for illumination and distribution. It is of pleasing out-look, light weight, reliable performance, high breaking capacity, quick trip. etc.

Standard

IEC60898

Type(wave form of the earth leakage sensed)

AC

Thermo-magnetic release characteristic

8-12In

Number of poles

1P+N, 2P, 3P,3P+N, 4P

Rated current(In)

63, 80, 100

Rated sensitivity I∆n

0.03, 0.1, 0.3A

Rated residual making and breaking capacity I∆n

2000A

Rated short-circuit capacity Icn

6000A

Break time under I∆n

≤0.1S

Rated frequency

50Hz

Rated impulse withstand voltage(1.2/50) Uimp

4000V

Dielectric TEST voltage, Freq for 1min

2.0Kv

Insulated voltage UI

500V

Pollution degree

3

Electrical life

1500

Mechanical life

8500

Contact position indicator

Yes

Protection degree

IP20

Ambient temperature

(with daily average≤35℃)

-5~+40℃

Storage temperature

-25~+70℃

Terminal connection type

Cable/Pin-type busbar

Terminal size top/bottom for cable

16~50mm²

6-1/10AWG

Terminal size top/bottom for busbar

16~35mm²

6-2AWG

Tightening torque

3.5 N*m

31 In-Ibs

Mounting connection

On din rail EN60715(35mm) by means of fast dip device from top

Meba rcbo circuit breaker MBR3410C frame and parts adopt plastic of high inflammable resistance and shock resistance for long service life. It is mainly used for overload and short circuit protection.

Categories
Residual Current Circuit Breaker With Over Current Protection

Meba residual current circuit breakers with overcurrent protection RCBOs MB161

Meba residual current circuit breakers with overcurrent protection RCBOs MB161

Construction and Feature
– Provides protection against earth fault/leakage current, short-circuit and overload
– High short-circuit capacity
– Provides complementary protection against direct contact by human body
– Effectively protects electric equipmet against insulating failure
– Contact position indication
– Provides protection against over-voltage
– Provides comprehensive protection to household and commercial distribution systems

Meba residual current circuit breakers with overcurrent protection RCBOs MB161

Technical Data
– Type: Electro-magnetic type
– Residual current characteristics: AC
– Pole NO.: 1P+N
– Tripping curve: B, C
– Rated short-circuit capacity: 10kA
– Rated current(A): 6, 10, 16, 20, 25, 32
– Rated voltage: 230/240V AC
– Rated frequency: 50/60Hz
– Rated residual operating current(mA): 0.03, 0.1
– Tripping duration: instantaneous ≤0.1s
– Electro-mechanical endurance: 4000 cycles
– Connection terminal: pillar terminal with clampWiring Diagram

Overall & Installation Dimensions

Categories
Residual Current Circuit Breaker With Over Current Protection

Meba residual current breaker with overload Protection RCBO breaker MBB2

Meba residual current breaker with overload Protection RCBO breaker MBB2

is suitable for the leakage protection in the line of AC 50/ 60Hz, rated voltage single phase 240V, three phase 240/415V and below, rated current up to 63A. When there is human electric shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage. Can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short-circuited, also as infrequent changeover of the line in normal situation. It complies with standard IEC/EN61009-1 and GB16917.1.

Meba residual current breaker with overload Protection RCBO breaker MBB2

1. Rated current: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A.
2. Rated residual operating current: 0.01A, 0.03A.
3. Tripping characteristics: C.
4. Icn: 6000A
5. Rated residual current operated making and breaking capacity Im: 500A
6. Rated residual non-operated current: Ino: 0.5InOverall and Mounting DimensionsDimensions B(mm)

1 pole 2 pole 3 pole 4 pole
54 72 117 135