LYD1 series surge protective device (hereinafter called SPD) is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As per the conditions of IEC61643-1:1998-02 standard, Class I surge protective device, it is category B surge protective device. SPD has two protection modes: MC and MD, SPD is in compliance with GB18802.1/IEC61643-1 standards.
Operation Elements

*SPD as only one side of terminals, able to prevent from being electric touching, indoor fixedly mounted, limiting voltage.
*SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector  can automatically  separate SPD from the network, meanwhile send an indication signal. The visible window show white color in normal service, if to be separated from network, it will show red color.
*  Maxi discharging current of each wire:  up to 100KA.
Installation
* To be mounted between LPZ0A or LPZ0B zone and LPZ1 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand soft copper conductor: 6 ~ 35 mm2.
* Generally it shall be mounted in the incoming side of main distribution panel or box.
* Earthing wire shall be of 10mm2 dual color conductor, its length not more than 500mm.

In order to eliminate the influence on normal service of power network due SPD is invalid, it shall  add fuse or  breaker  to  be  series connected in L line. (NB:selected accordingto standard current In)

Technical Parameter:
Categories
Surge Protective Device

Meba surge protection devices MBS8

Meba surge protection devices MBS8

Meba surge protection devices MBS8

MBS8 series surge protective device (hereinafter called SPD) is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As per the conditions of IEC61643-1:1998-02 standard, Class I surge protective device, it is category B surge protective device. SPD has two protection modes: MC and MD, SPD is in compliance with GB18802.1/IEC61643-1 standards。

Operation Elements
* SPD as only one side of terminals, able to prevent from being electric touching, indoor fixedly mounted, limiting voltage.
*SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector  can automatically  separate SPD from the network, meanwhile send an indication signal. The visible window show white color in normal service, if to be separated from network, it will show red color.
* Maxi discharging current of each wire:  up to 100KA.

Installation

* To be mounted between LPZ0A or LPZ0B zone and LPZ1 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand soft copper conductor: 6 ~ 35 mm2.
*Generally it shall be mounted in the incoming side of main distribution panel or box.
*Earthing wire shall be of 10mm2 dual color conductor, its length not more than 500mm.

In order to eliminate the influence on normal service of power network due SPD is invalid, it shall  add fuse or  breaker  to  be  series connected in L line. (NB:selected accordingto standard current In)

Technical Parameter:
Categories
Surge Protective Device

Meba power surge protection MBS10

Meba power surge protection MBS10

Meba power surge protection MBS10  (hereinafter called SPD) is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As per the conditions of IEC61643-1:1998-02 standard, Class I surge protective device, it is category B surge protective device. SPD has two protection modes: MC and MD, SPD is in compliance with GB18802.1/IEC61643-1 standards.

Operation Elements

* SPD as only one side of terminals, able to prevent from being electric touching, indoor fixedly mounted, limiting voltage.
* SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector  can automatically  separate SPD from the network, meanwhile send an indication signal. The visible window show white color in normal service, if to be separated from network, it will show red color.
*Maxi discharging current of each wire:  up to 100KA.

Installation
* To be mounted between LPZ0A or LPZ0B zone and LPZ1 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand soft copper conductor: 6 ~ 35 mm2.
*Generally it shall be mounted in the incoming side of main distribution panel or box.
*Earthing wire shall be of 10mm2 dual color conductor, its length not more than 500mm.

In order to eliminate the influence on normal service of power network due SPD is invalid, it shall  add fuse or  breaker  to  be  series connected in L line. (NB:selected accordingto standard current In)

 

 

Technical Parameter:
Categories
Surge Protective Device

Meba power surge MBS21W

Meba power surge MBS21W

Meba power surge MBS21W (hereinafter called SPD) is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As per the conditions of IEC61643-1:1998-02 standard, Class I surge protective device, it is category B surge protective device. SPD has two protection modes: MC and MD, SPD is in compliance with GB18802.1/IEC61643-1 standards.
Operation Elements
* SPD as only one side of terminals, able to prevent from being electric touching, indoor fixedly mounted, limiting voltage.
*SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector  can automatically  separate SPD from the network, meanwhile send an indication signal. The visible window show white color in normal service, if to be separated from network, it will show red color.
*Maxi discharging current of each wire:  up to 100KA.

Installation

* To be mounted between LPZ0A or LPZ0B zone and LPZ1 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand soft copper conductor: 6 ~ 35 mm2.
*Generally it shall be mounted in the incoming side of main distribution panel or box.
*Earthing wire shall be of 10mm2 dual color conductor, its length not more than 500mm.

In order to eliminate the influence on normal service of power network due SPD is invalid, it shall  add fuse or  breaker  to  be  series connected in L line. (NB:selected accordingto standard current In)

 

 

Technical Parameter:
Categories
Surge Protective Device

Meba surge supressor MBD3-40

Meba surge supressor MBD3-40(hereinafter called SPD)  is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As per the conditions of IEC61643-1:1998-02 standard, Class I surge protective device, it is category B surge protective device.
SPD meets with GB18802.1/IEC61643-1 standards.

Meba surge supressor MBD3-40

Technical Parameter

Operation Elements
Single pole structure, single pole or three poles combined SPD available.
SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector can automatically separate SPD from the network, meanwhile send an indication signal.
The visible window show white color in normal service, if to be separated from network, it will show red color. It can adopt Kelvin wiring mode. Large current carrying capacity, fast response time, low residual voltage.

Installation
– Category B surge protective device (SPD), used in the connection between equal potential electrodes while thunder occur.
– To be mounted: between LPZ0A or LPZ0B zone and LPZ1 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand soft copper conductor: 2.5 – 35mm2.
– Generally to be installed in low voltage main incoming distribution panel, overhead incoming.
– As required, the user can assemble single pole or three poles surge protective device freely.
– Generally to be installed in low voltage main incoming distribution panel, earthing wire shall be dual color multi-strand soft copper conductor more than 16 mm2

Model and Signification

Technical Parameter

Model and specification MBD3-15 MBD3-40 MBD3-65 MBD3-80 MBD3-100 MBD3-120
Maxi continuous operating voltage 420 275 420 275 420 275 420 275 420 275 420 275
Voltage protective level 1.2 1.0 1.8 1.5 2.5 1.5 2.5 1.8 2.8 2.0 3.0 2.0
Maxi discharging current 15 45 65 80 100 120
Nominal discharging current 5 15 30 40 50 60
Response time <25
Indication of invalidation Aging invalidation: white: Normal, red: invalidation
Protection grade IP20
Application Protection for in line

Outside Size Fig

Categories
Surge Protective Device

Meba surge protection MBD1-D20

MBD1-D series surge protective device (hereinafter called SPD) is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As per the conditions of IEC61643-1:1998-02 standard, Class III surge protective device, it is category D surge protective device.
SPD has two protection modes: MC and MD
SPD is in compliance with GB18802.1/IEC61643-1 standards.

Meba surge protection MBD1-D20

Technical Parameter

Operation Elements
SPD as only one side of terminals, able to prevent from being electric touching, indoor fixedly mounted, limiting voltage.
SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector can automatically separate SPD from the network, meanwhile send an indication signal. The visi ble window show white color in normal service, if to be separated from network, it will show red color.
1P+N, 2P +N, 3P+N SPD consist of 1P 2P 3P SPD and NPE neutral and earthing protection modules, used in the power supply system of TN-S , TN-C-S and etc.

Installation
– To be mounted between LPZ1 or LPZ2 zone and LPZ3 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand s oft copper conductor : 2.5 – 35 mm2.
– Every pole of MBD shall be protected by fuse or mini circuit breaker.
– It is mounted in distribution boxes of living house, computer center, communication equipment, electronic equipment and control equipment or nearest socket box.

Model and Signification

Technical Parameter

Model and specification MBD1-D20 MBD1-D10
Maxi continuous operating voltage 750 420 385 320 275 750 420 385 320 275
Voltage protective level 3.0 2.0 1.8 1.6 1.5 2.0 1.6 1.3 1.2 1.0
Maxi discharging current 20 10
Nominal discharging current 10 5
Response time <25
Protection grade IP20
Indication of invalidation Aging invalidation: white: Normal, red: invalidation
Application Several protection for in line
Remote signal Function Can also picking
Remarks Other maxi continuous operating voltage Can be customize

Principle Diagrams

Outside Size Fig

 

Categories
Surge Protective Device

Meba surge arrestor MBD1-B60

MBD1-B series surge protective device (hereinafter called SPD) is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As per the conditions of IEC61643-1:1998-02 standard, Class I surge protective device, it is category B surge protective device. SPD has two protection modes: MC and MD
SPD is in compliance with GB18802.1/IEC61643-1 standards.

Meba surge arrestor MBD1-B60

 

Technical Parameter

Operation Elements
In three phases and four wires system, all three phase lines and one neutral line to earthing line have SPD to be protected, in normal service, the SPD is at the state of high resistance, when network produce surging over-voltage due to thunder or other reasons, SPD will be conductive within short time (ns), lead surging voltage into ground, consequently to protect the electric appliances of network. After surging voltage passed by SPD, and disappeared, SPD recover in high resistance. It will not have influence on the normal service of network.

Installation
– The SPD need not to be adjusted after in-stalled according to requirement.
– It can automatically protect the power net-work after proper installation.
– On services it need periodically check if SPD is invalid or not, meanwhile check red indicator of fuse lighting or not, please replace the invalid element on time.

Model and Signification

Technical Parameter

Model and specification MBD1-B60 MBD1-B80 MBD1-B100
Maxi continuous operating voltage 750 420 385 275 420 385 320 275 420 385 320 275
Voltage protective level 3.5 2.2 2.0 1.6 2.5 2.3 2.0 1.8 3.0 3.0 2.5 2
Maxi discharging current 60 80 100
Nominal discharging current 30 40 60
Response time <25
Protection grade IP20
Indication of invalidation Aging invalidation: white: Normal, red: invalidation
Application Primary protection for in line
Remote signal Function Can also picking
Remarks Other maxi continuous operating voltage Can be customize

Principle Diagrams

Outside Size Fig

Categories
Surge Protective Device

Meba surge arrester MBD1A

 The acoustic-optical alarm module shall operate with module surge protective device, used in AC 50/60Hz, 220V/385V power supply system, the protection grade and number of poles (1P 2P 3P 4P) ar e determined by user.
Once power source module is out of operation, acoustic alarm sounds, red LED flash, meanwhile it will give a command signal to a terminal for alarm against in validity, which has NO, NC contacts, namely NC marked with 1, 2, NO marked with 1, 3; while alarming, push black button to cancel the alarm sound temporarily, red LED continue flashing, if fault module is not replaced, the acoustic alarm will sound again, afte r to replace the fault module, red LED go out, SPD return to normal operation.

Meba surge arrester MBD1A

 

Model and Signification

MBD1A-C series acoustic-optical alarm surge protective device
Disconnector built in SPD, when SPD is in-valid due to breakdown come from overheating, over-current, the disconnector will cut off the SPD automatically and give indication signal of changed color. When SPD work normally, the visible window of module will show green, once in valid, it wi ll show red, and produce acousticoptical alarm via connecting rod on the base, indicating the status of SPD is in normal service, aging, tripped temperature fuse or over-current and etc.

Technical Parameter

Model and specification MBD1A-B MBD1A-C MBD1A-D
Maxi carrying capacity 80 60 40 20 10
Nomial carrying capacity 40 30 20 10 5

With sound and light alarm module appearance and size (mm)

 

Categories
Surge Protective Device

Meba power surge MBX-R(L)24

MBX-R/L two-stage circuit consists of gas discharging tube, pie zore-sistance and clamping diode, with advantages of large discharging capacity, short clamping time and low protection level.
MBX-R/L protector can be mounted on 35mm rail of different standard switching box or distribution box. It does not need screws for connecting with terminal.

Meba power surge MBX-R(L)24

 

Technical Parameter

Arrester MBX-R/L
Mounting position 13
Nominal voltage 5V 6V 12V 24V 48V
Max. continuous operating voltage 7V 9V 15V 30V 51V
Voltage protective level ≤13V ≤20V ≤30V ≤51V ≤100V
Rated loading current of category R 0.2A
Rated loading current of category L 1.0A
Nominal discharging current 10KA
Series connected resistance of each line of category R 15
Series connected inductance of each line of category L 100H
Cross sectional area of connected conductor 0.14-2.5mm2
Peel-off length for the wire to be connected 6-7mm
Color Grey
Material Fire resistant reinforced PC
Applicable standard GB18802.2 IEC61643-21