Drop-out fuses are electrical devices that protect high-voltage power equipment from lightning damage. Voltage ranges include 15KV, 24KV/27KV, 33KV, etc.; currents include 100A and 200A.

Item 1 10KV-15KV

TYPE MB-12/100 MB-12/200 Notes
Rated voltage(V) 10-15 10-15 ceramic insulator.
Rated current(A) 100 200
Breaking current(A) 10,000 12,000
Impulse voltage(kV) 110 110
Power frequency withstand volatege(kV) 42 42
Creepage distance (mm) 250 250
Weight (kg) 7.0 7.0
Dimensions (cm) 38.5*34.5*10.5 38.5*34.5*10.5

Item 2  15KV-27KV

TYPE MB-27/100A MB-27/200A Notes
Rated voltage(V) 15-27 15-27 ceramic insulator
Rated current(A) 100 200
Breaking current(A) 10,000 10,000
Impulse voltage(kV) 125 125
Power frequency withstand volatege(kV) 45 45
Creepage distance (mm) 355 355
Weight (kg) 8.8 8.8
Dimensions (cm) 51.5*34*12 51.5*34*12

Item 3  33KV-36KV

TYPE MB-33/100 MB-33/200 Notes
Rated voltage(V) 33 33 ceramic insulator
Rated current(A) 100 200
Breaking current(A) 6000 8000
Impulse voltage(kV) 170 170
Power frequency withstand volatege(kV) 70 70
Creepage distance (mm) 660 660
Weight (kg) 15 15
Dimensions (cm) 56*38*11.5 56.38*14.5

Item 4  33KV-36KV

TYPE MB-36/100 MB-36/200 Notes
Rated voltage(V) 36 36 Silicone insulator
Rated current(A) 100 200
Breaking current(A) 10000 12000
Impulse voltage(kV) 170 170
Power frequency withstand volatege(kV) 70 70
Creepage distance (mm) 720 720
Weight (kg) 5 5
Dimensions (cm) 61*34*11.5 61*34*11.5
Welcome

If you would like a quotation or further information on this product, please fill in the form below and we will reply to you within 1 working day.

Fill out my online form.