CLASSIFICATION |
Floatless Relay |
|
MODEL |
AFR-1 |
|
DIMESIONS(mm) |
61H*49W*70D |
|
SOCKET TYPE |
PF083A |
|
SENSING |
GENDRAL |
AFR-1 |
HIGH SENSING |
AFR-1H |
|
LONG DISTANCE |
AFR-1L |
|
LOW DENSITY |
AFR-1D |
|
TWOLINES |
AFR-1R |
|
RATED VOLTAGE |
AC:110V,220V,240V,50/60HZ |
|
INDICATOR OPERATING |
Two LED’s use fro two status |
|
OPERATE VOLTAGE |
85~110%of rated voltage |
|
SECND VOLTAGE |
8VAC (except highsensing 24VAC) |
|
OPERATE RESISTANCE |
4K MIN.(GENERAL) |
|
RELEASE RESISTANCE |
15K MIN.(GENERAL) |
|
RESPONSE TIM |
OPERATE:80 MSEC MAX.RELEASE:160MSEC MAX. |
|
CONTACT RATING |
5A,250VAC(RESISTIVELOAD) |
|
LEGTH OF CABLE |
1KMMAX.(GENERAL) |
|
LIFE |
MECHANICAL |
5*106TIMES MIN |
ELECTRICAL |
105 times min |
|
INSULATION RESISTANCE |
100M (DC 500V)MIN |
|
DIELECTRIC STRENGTH |
1500VAC,50/60HZ,FOR 1MINUTE |
|
CONSUMED POWER |
3.2VA |
|
AMBIENT TEMPERATURE |
-10℃~+55℃ |
|
AMBIENT HUMIDITY |
45~85%RH |
|
WEIGHT |
200g |