Meba mcb rating MB626C adopts advanced design technology, it has protective function as shortage as overload, and are used in lighting distribution system industry, commerce and dwelling, and protecting fractional electric motors, and Meba mcb rating MB626C also have many merits of high protective grade(up to IP20), high breaking capacity, reliable sensitive action, convenient, multiple assembling, long life etc. They are mainly adapted to the circuit of AC 50Hz, 230V in single pole; 400V in double, three, four poles for protecting overload and short circuit, meanwhile Meba mcb rating MB626C  are also used in turning on or off the electric apparatus and lighting circuit under the normal condition.

Meba mcb rating MB626C

Technical parameters:

Against overload and short circuit in commercial, household and electric equipment installation. The product is suitable for non-frequently making and breaking operation.

Basic specification and main parameters

Frame class 63A
Rated working voltage 240V/415V
Rated frequency 50/60Hz
Rated working current 1,3,6,10,16,20,25,32,40,50,63A
Making and breaking capacity 6000A(6~40A),4500A(50,63A)
Release type B,C,D
Poles 1,2,3,4P
Mechanical life 20000
Electric life 4000

 

The over-current tripping unit protection feature

Sequence
NO .
Release Test
current I/In
Start state Tripping
time
Expected
results
1 B,C,D 1.13In Cold state t≤1h Not tripping
2 B,C,D 1.45In Start right after
the serial NO .
1 test
t<1h Tripping
3 B,C,D 2.55In Cold state 1s Tripping
4 B
C
D
3In
5In
10In
Cold state t≤0.1s Not tripping
5 B
C
D
5In
10In
20In
Cold state t<0.1s Tripping
[Download not found]
Welcome

If you would like a quotation or further information on this product, please fill in the form below and we will reply to you within 1 working day.

Fill out my online form.