Miniature Circuit Breaker

Meba breaker C47 type

Meba breaker C47 type  is mainly used in AC50/60Hz single pole 230V or two, three, four pole 400V voltage for overload and short-circuit protection as well as for un-frequent on-and-off switching electric equipment and lighting circuit under normal condition, the product is suitable for industry, business, building, residence, etc. It’s conformity with GB10963, IEC60898 standards.

Meba breaker C47 type

Standard IEC60898
Number of poles 1P, 2P, 3P, 4P
Rated current(In) 6, 10, 16, 20, 25, 32, 40, 50, 63
Rated voltage(Un) AC240/415V
Rated frequency 50/60Hz
Tripping curve B, C, D
Release action characteristics Time delay 1.13In>1h Non-trip
1.45In<1h trip
2.55In 1s-60S trip
Instantaneous(Curve C) 5In>0.1s Non-trip
10In<0.1s trip
Magnetic releases operate B curve:between 3 and 5In
C curve:between 5 and 10In
D curve:between 10 and 15In
Rated breaking capacity (Lcn) 3000A
Endurance >2500
Circumstance temperature -5 to +40℃
Electrical life >6000times
Mechanical life 20000 times
Tropical ration Treatment 2(RH95%, at 55℃)
Protection degree IP20
Categories
Fuse Modular Devices

Meba fuses MBR47

Meba fuses MBR47 have protective function as shortage as overload, and used in lighting distribution system, industry, commerce, and protect fractional electric motors. And they also have many merits of high protective grade(up to IP20),high break capacity, reliable sensitive action, convenient, multi-pole assembling, long life etc. They are mainly adapted to the circuit of AC 50Hz,230V in single pole,400V in double, three, four poles for protecting overload and short circuit. Meanwhile, they are also used in turning on or off the electric apparatus and lighting circuit under the normal condition.

Meba fuses MBR47
 
Manufacturing Standards IEC 60898 IEC60947
Tropicalization Relative Humidity 93% RH at 25℃
Room Temperature 10℃ a 60℃
Electrical Properties Rated at 40℃ A 6/10/16/20/25/32/40/50/63
Rated operating voltage at 40℃ Vac 240/415
Nominal Frequency Hz 50/60
Interrupting Capacity at 230V kA 6
Operating temperature 40
Degree of Protection IP20
Number of poles 1/2/3/4
Conductor cross section (minimum allowable) mm2 25
Minimum number of power moves 4000
Minimum number of mechanical operations 10000
Operation curve B/C/D
Current Trip Curve A 5 a 10 In
Characteristic Intervention attach
Type Of Assembly FOR RIEL DIN 35 mm