Meba lightning surge protection MBS2

Meba lightning surge protection MBS2

Meba lightning surge protection MBS2

□ MBS2series surge protective device (hereinafter called SPD) is developed no basis of absorbing foreign latest technology, used in power supply system of AC 50/60Hz, rated voltage 380V and below, to protect from direct and indirect lightning impulse and other transient over voltage.
□ SPD has two protection modes: MC and MD。
□ SPD is in compliance with GB18802.1/IEC61643-1 standards
Operation Elements
□ SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector can automatically separate SPD from the network, meanwhile send an indication signal. The visible window show white color in normal service, if to be sepa-rated from network, it will show red color.
Installation
To be mounted between LPZOB or LPZ1 zone and LPZ2 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand soft copper conductor: 2.5~ 35 mm2.Every pole of SPD shall be protected by fuse or mini circuit breaker. As required, the user can assemble single pole or three poles
surge protective device freely.

Technical Parameter:
Model and specification MBS2-65 MBS2-40 MBS2-15 MBS2-8
Maxi continuous operating voltageUc(VAC) 420 275 420 275 420 275 420 275
voltage protective level Up(KV) ≤ 2.5 2 2 1.2 1.5 1 1.2 0.8
Max discharging current(8/20us)Imax(KA) 65 40 15 8
Nominal discharging current (8/20us)In(KA) 30 15 5 2
Response time(ns) <25
Indication of invalidation Aging invalidation:White:Normal,Red: Invalidation
Protection grade IP20
Application Protection for in line
Remote signal function If need, can supply
Categories
Surge Protective Device

Meba lightning protection MBS1201

Meba lightning protection MBS1201

Meba lightning protection MBS1201 (hereinafter called SPD) is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As per the conditions of IEC61643-1:1998-02 standard, Class I surge protective device, it is category B surge protective device. SPD has two protection modes: MC and MD, SPD is in compliance with GB18802.1/IEC61643-1 standards.
Operation Elements
* SPD as only one side of terminals, able to prevent from being electric touching, indoor fixedly mounted, limiting voltage.
*SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector  can automatically  separate SPD from the network, meanwhile send an indication signal. The visible window show white color in normal service, if to be separated from network, it will show red color.
*Maxi discharging current of each wire:  up to 100KA.

Installation
* To be mounted between LPZ0A or LPZ0B zone and LPZ1 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand soft copper conductor: 6 ~ 35 mm2.
*Generally it shall be mounted in the incoming side of main distribution panel or box.
*Earthing wire shall be of 10mm2 dual color conductor, its length not more than 500mm.

In order to eliminate the influence on normal service of power network due SPD is invalid, it shall  add fuse or  breaker  to  be  series connected in L line. (NB:selected accordingto standard current In)

Technical Parameter:
Categories
Surge Protective Device

Meba lightning protection MBD4-40

Meba lightning protection MBD4-40 (hereinafter called SPD)   is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage.SPD meets with GB18802.1/IEC61643-1 standard.

Operation Elements
SPD as only one side of terminals, able to prevent from being electric touching, indoor fixedly mounted, limiting voltage. SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector can automatically separate SPD from the network, meanwhile send an indication signal. The visible window show white color in normal service, if to be separated from network, it will show red color. Fast response time, low residual voltage.

Meba lightning protection MBD4-40

Installation
– To be mounted in joint of LPZ1 or LPZ2 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand soft copper conductor: 2.5 – 35 mm2.
– Every pole of SPD shall be protected by fuse or mini circuit breaker.

The Contact
SPD can provide the NO contact for remote communication, if one or more modules of SPD is invalid, the NO and NC contact will be closed and send fault information.

Model and Signification

Technical Parameter

Model and specification MBD4-20 MBD4-40
Maxi continuous operating voltage 420 275 420 275
Voltage protective level 1.8 1.2 2.0 1.5
Maxi discharging current 20 40
Nominal discharging current 10 20
Response time <25
Protection grade IP20
Indication of invalidation Aging invalidation: white: Normal, red: invalidation
Application Protection for in line
Remote signal Function Can also picking
Remarks Other maxi continuous working voltage Uc (AC) can be supplied if required.

Outside Size Fig