Categories
Miniature Circuit Breaker

Meba mcb rccb MB1-63-50A

Meba mcb rccb MB1-63-50A

Meba mcb rccb MB1-63-50A , this series Miniature Circuit Breaker is nice in appearance, reasonable in structure, sound in feature and high in breaking capacity. Installed with standard din rail, it is convenient and easy in usage. It is mainly used in the line of AC 50/60Hz, rated working voltage to 240V/415V, and rated current to 63A as protection against overload and short-circuit. It can be used as infrequent on-and-off operation and changeover.
It complies with standard of GB10963 and IEC/EN60898.

Meba mcb rccb MB1-63-50A

Technical parameters

Frame class

63A

Rated working voltage

240V/415V

Rated frequency

50/60Hz

Rated working current

1、3、6、10、16、20、25、32、40、50、63A

Making and breaking capacity

6000A(6~40A),4500A(50、63A)

Release type

B、C、D

Poles

1、2、3、4P

Mechanical life

20000

Electric life

4000

The over-current tripping unit protection feature   

Sequence
NO .

Release

Test
current I/In

Start state

Tripping
time

Expected
result

1

B、C、D

1.13In

Cold state

t≤1h

Not tripping

2

B、C、D

1.45In

Start right after
the serial NO .
1 test

t<1h

Tripping

3

B、C、D

2.55In

Cold state

1s<t<60s

Tripping

4

B
C
D

3In
5In
10In

Cold state

t≤0.1s

Not tripping

5

B
C
D

5In
10In
20In

Cold state

t<0.1s

Tripping

 

Dimensions(mm)

Meba-mcb-and-mccb-MB1-63-40A

Characteristics curve

Meba mcb and mccb MB1-63-40A Characteristics curve

Categories
Miniature Circuit Breaker

Meba mcb rccb GN type

Meba mcb rccb GN type  major export to South America, Middle East market, has light weight, small size, novel structure and excellent performance. They are mounted in the metal distribution board and used in guesthouses. block of fiats, high buildings, squares, airports, railway stations, plants and enterprises etc, in AC circuits 240V(single pole)up to 415V(3poie)50Hz for protection of overload short circuit and for circuit changeover in lighting system. Breaking capacity is 3KA. The items comply with BS&NEMA STANDARD.

Feature:

MAGNETIC COIL: ensures the switching of short-circuit, speaking within the following ranges: 5 to 10 times rated current (Type C), 3 to 5 times rated current ( Type B ), 10 to 20 times rated current ( Type D )

BIMETAL: ensures the breaker trip when overloaded.

ARC CHAMBER: effectively dissipates the electric arc that is generated by the opening contacts of the trigger mechanism in the presence of an overload or short circuit.

Meba mcb rccb GN type

Technical parameters

ropicalization Relative Humidity 93% RH at 25
Room Temperature 10 a 60
Electrical Properties Rated at 40 A 6/10/15/20/30/40/50/63
Rated operating voltage at 40 Vac 120/240/415
Nominal Frequency Hz 50/60
Interrupting Capacity at 230V kA 3
Operating temperature -5 a +40
Degree of Protection IP20
Number of poles 1,2,3,4
Conductor cross section (minimum allowable) mm2 25
Minimum number of power moves 4000
Minimum number of mechanical operations 6000
Operation curve B/C/D
Current Trip Curve A Type B 3a 5 In
Type C 5 a 10 In
Type D 10 a 14 In
Characteristic Intervention attach
Type Of Assembly NEMA Type
Features MAGNETIC COIL: ensures the switching of short-circuit, speaking within the following ranges: 5 to 10 times rated current (Type C), 10 to 14 times rated current ( Type D )
BIMETAL: ensures the breaker trip when overloaded.
ARC CHAMBER: effectively dissipates the electric arc that is generated by the opening contacts of the trigger mechanism in the presence of an overload or short circuit.