Categories
Residual Current Circuit Breaker

Meba RCCB Electrical Breaker MB090

Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: MB090
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P

Application:

1. MB090 RCD provide the function of isolation switching and earth leakage protection of electrical circuits.

2. They open a circuit automatically in the event of an earth fault between phase and earth and/or netural and earth. A wide range of current ratings and sensitivities are available.

3. Suitable for domestic, commercial and industrial applications.

Merits:

Good quality , high breaking capability, updated structure,quick trip and guide installation, competitive price,excellent and safe performance,beautiful and compact appearance, etc .

Mounting Requirements:

1. Circumstance temperature -5°C ~ +40°C, average temperature not exceeding 35°C.
2. Altitude above sea level less than 2000 m.
3. Humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
4. Installation class II or III.
5. Pollution class 2.
6. Installation method DIN Rail mounting type.
7. The external magnetism shall not be more than 5 times of terrestrial one.
8. Product shall be installed vertically at the place where there shall be no severe impact and vibration. The product is switched on when the handle is at upper position.

Mode

Electro-magnetic type, electronic type

Residual current characteristics

A, AC

Pole No.

2, 4

Rated making and breaking capacity

630A

Rated current(A)

16 25 40 63A

Rated voltage

240/415V AC

Rated frequency

50/60Hz

Rated residual operating current IΔn(mA)

10, 30, 100, 300, 500

Rated residual non operating current IΔno

0.5IΔn

Rated conditional breaking current Inc

6000A

Rated conditional residual breaking current IΔc

6000A

Tripping duration

Instantaneous tripping≤0.1s

Residual tripping current range

0.5IΔn~IΔn

Electro-mechanical endurance

4000 cycles

Connection capacity

Rigid conductor up to 25mm2

Connection terminal

Screw terminal

Pillar terminal with clamp

Fastening torque

2.0 Nm

Installation

On symmetrical DIN rail 35mm

Panel mounting

Dimensions:

MB089 RCCB Dimension

[Download not found]Meba RCCB Electrical Breaker MB090 shall be installed vertically at the place where there shall be no severe impact and vibration. The product is switched on when the handle is at upper position. 

Categories
Residual Current Circuit Breaker With Over Current Protection

Meba Electrical Rccb DZ30L

Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: DZ30L-32
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: DPN

Specification:

1. DPNL(DZ30L)earth leakage circuit breaker is used for the protection, against electrical leakage in the circuit of 50Hz or 60Hz, rated voltage single-phase 240V, three-phase 415V, rated current up to 32A.
2. When somebody gets an electric shock or the residual current of the circuit exceeds the fixed value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal safety and preventing the equipment from the fault resulted from the residual current
3. With this function, the ELCB can protect the circuit against overload and short circuit or can be used for the unfrequent switch over of the circuit under normal conditions. It conforms to IEC/EN 61009

Merits:

Good quality , high breaking capability, updated structure,quick trip and guide installation, competitive price,excellent and safe performance,beautiful and compact appearance, etc .

1. Residual current device with overcurrent protection
2. Combine in residual current device function and MCB over-current protection function
3. Short circuit capacity: 3KA
4. Rated current(A): 6,16,20,25,32A
5. Rated leakage operating current(mA): 30,100,300mA
6. AC types, B-C characteristic
7. Modular Din Rail products 35mm.

[Download not found] Meba Electrical Rccb DZ30L  protect human from the fault of electric because of over-current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 32A.