Categories
Miniature Circuit Breaker

Meba mcb mccb difference MB1-63-6A

Meba mcb mccb difference MB1-63-6A

Meba mcb mccb difference MB1-63-6A , this series Miniature Circuit Breaker is nice in appearance, reasonable in structure, sound in feature and high in breaking capacity. Installed with standard din rail, it is convenient and easy in usage. It is mainly used in the line of AC 50/60Hz, rated working voltage to 240V/415V, and rated current to 63A as protection against overload and short-circuit. It can be used as infrequent on-and-off operation and changeover.
It complies with standard of GB10963 and IEC/EN60898.

Meba mcb mccb difference MB1-63-6A

Technical parameters

Frame class

63A

Rated working voltage

240V/415V

Rated frequency

50/60Hz

Rated working current

1、3、6、10、16、20、25、32、40、50、63A

Making and breaking capacity

6000A(6~40A),4500A(50、63A)

Release type

B、C、D

Poles

1、2、3、4P

Mechanical life

20000

Electric life

4000

The over-current tripping unit protection feature   

Sequence
NO .

Release

Test
current I/In

Start state

Tripping
time

Expected
result

1

B、C、D

1.13In

Cold state

t≤1h

Not tripping

2

B、C、D

1.45In

Start right after
the serial NO .
1 test

t<1h

Tripping

3

B、C、D

2.55In

Cold state

1s<t<60s

Tripping

4

B
C
D

3In
5In
10In

Cold state

t≤0.1s

Not tripping

5

B
C
D

5In
10In
20In

Cold state

t<0.1s

Tripping

 

Dimensions(mm)

Meba-mcb-and-mccb-MB1-63-40A

Characteristics curve

Meba mcb and mccb MB1-63-40A Characteristics curve

Categories
G series Moulded Case Circuit Breaker

Meba MCB MCCB Difference HKW-400

Meba MCB MCCB Difference HKW-400

·Brief description
G series moulded case circuit breaker not only has compact volume than normal circuit breaker or fuse, but
also supply more advanced performance. Advantages as following:

■Easy installation accessory

■Easy installation accessory

■20A-2500A can equip with electronic trip

■Built in 20A earth fault protection

·Application
HKW-400 is one kind of latest developed molded case circuit breaker in our factory, it is according to cutler-hammer technology, at present we mainly export to South America and Middle East countries, quality is satisfied by our customers.

·Operating mechanism
1.
G circuit breaker adopts shaft operation feature, this shaft can instruct circuit breaker’s  working condition: ON OFF and PIPPED.

2. When circuit breaker appear overloading, short circuit, shunt or under voltage trip action, shaft will jump to TRIPPED (trip) position, at this time, if need to re-switch on must push shaft to RESET position.

3. On both sides of shaft on EG and RG frame there will have 2 windows, which direct circuit breaker’s  working condition, red, green and white each correspondence  to: On/OFF/TRIPPED.

Type G F J K L
Frame Current(A) 100 225 250 400 630
Culter-hammer Specifications GWF FW HFW FWH HFWF HJW HKW HLW
Rated Current(A) 16-100 16-225 125-250 125-400 315-600
Number of Poles 3 Poles
Breaking Capacity(kA, rms), AC50/60Hz
IEC60947-2 220-240V AC Icu 65 85 100 85 100 100 100 100
Ics 33 85 100 85 100 100 100 100
380-415V AC Icu 25 40 70 40 70 70 70 70
Ics 13 40 70 40 70 70 70 70
660-690V AC Icu 12 14 12 14 18 25 25
Ics 6 7 6 7 9 13 13
250V DC Icu 10 10 20 10 20 20 20 20
Ics 5 5 10 5 10 10 10 10
NEMA 240V AC 65 65 100 65 100 100 100 100
480VAC 22 25 65 25 65 65 65 65
600VAC 18 25 18 25 25 35 35
Rated Insulation Voltage Main Circuit 750VAC
Auxiliary Circuit 690VAC
Uimp Main Circuit 6kV 8kV
Auxiliary Circuit 4kV
Rated Working Voltage, Ue 440 690
Ambient Temperature From -20 to +70
Size(mm) H 123.8 152.4 177.8 280 273
W 76.2 105 105 140 210
D 66.7 86 103 104 104
Weight(kg) 1 2.4 5.2 6.1 9.4

Working condition:
1.The altitude not exceeding 2000m
2.The ambient temperature is from +40°Cto -5°C
3.Ambient environment is free from explosive danger and air or dust, which may cause corrosion of metal or weakness of insulation.
4.Ambient environment is free from erosion of rain or snow.
5.Pollution degree 3
6.Over-voltage category III

[Download not found] Meba MCB MCCB Difference HKW-400 is big ampere circuit breaker  with high breaking capacity match with RCCB, MCB  use  to protection power distribution equipment safety.

Categories
NF Moulded Case Circuit Breaker

Meba Moulded Case Circuit Breaker NF100-CP

1. NF series thermal magnetic type molded case circuit breaker, developed from Mitsubishi type, included NF-CS, NF-SS, NF-CP, NF-SP, NF-HP, NF-CW series.

2. Rated working voltage 690V, 50HZ or 60HZ, and rated working current from 3A to 800A.

3. It mainly used in distributing electric energy and protect the electrical circuit and power equipment from damages caused by overload, short circuit or under-voltage in the distribution network.

4. It complies with IEC60947-2 and GB14048.2 standards.

Working Conditions and Mounting Environments
1. The altitude should be less than 2000m
2. The ambient medium temperature should within -5℃ to +40℃
3. This moulded case circuit breaker is resistant to moisture, salt fog, nuclear radiation, and mildew
4. The maximum tilt angle is 22.5°
5. MCCB can still work reliably if the product is subjected to vibration from ships or earthquakes(4g)

Parameters of NF-100 Moulded Case Circuit Breaker

Frame Current(A) 100
Model NF-100C NF-100S NF-100M NF-100H
Rated Current in(A) 16,20,32,40,50,63,80,100A
Poles 2 3 4 2 3 4 2 3 4 2 3 4
Rated Voltage Ue(V) AC400
Rated Insulation Voltage Ui(V) AC690
(KA)AC400 Short-Circuit Interrupting Capacity Icu/Ics 15/7.5 50/25 50/35 80/50
Operation Life(cycle) Power on 3000
Power off 7000
Dimensions(mm) a 60 90 120 60 90 120 90 90 120 90 90 120
b 155 155 155 155
c 68 68 68 83
ca 90 90 90 105
Weight(kg) 0.7 1.0 0.75 1.1 1.4 0.75 1.1 1.4 0.75 1.1 1.4
Electrical-operation Device(MD)
External Rotary Handle
Automatic Tripping Device thermal-magnetic thermal-magnetic thermal-magnetic thermal-magnetic

[Download not found]Meba Moulded Case Circuit Breaker NF100-CP is update thermal magnetic type mccb max 100A against overload & short circuit.