Meba power surge MBS21W

Meba power surge MBS21W

Meba power surge MBS21W (hereinafter called SPD) is suitably used in the IT, TT, TN-C, TN-S, TN-C-S and etc power supply system of AC 50/60Hz, rated voltage up to 380V, to protect from direct and indirect lightning impulse and other transient over voltage. As per the conditions of IEC61643-1:1998-02 standard, Class I surge protective device, it is category B surge protective device. SPD has two protection modes: MC and MD, SPD is in compliance with GB18802.1/IEC61643-1 standards.
Operation Elements
* SPD as only one side of terminals, able to prevent from being electric touching, indoor fixedly mounted, limiting voltage.
*SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector  can automatically  separate SPD from the network, meanwhile send an indication signal. The visible window show white color in normal service, if to be separated from network, it will show red color.
*Maxi discharging current of each wire:  up to 100KA.

Installation

* To be mounted between LPZ0A or LPZ0B zone and LPZ1 zone, adopts 35mm standard mounting rail. The cross sectional area of multi-strand soft copper conductor: 6 ~ 35 mm2.
*Generally it shall be mounted in the incoming side of main distribution panel or box.
*Earthing wire shall be of 10mm2 dual color conductor, its length not more than 500mm.

In order to eliminate the influence on normal service of power network due SPD is invalid, it shall  add fuse or  breaker  to  be  series connected in L line. (NB:selected accordingto standard current In)

 

 

Technical Parameter:
Categories
Surge Protective Device

Meba power surge MBX-R(L)24

MBX-R/L two-stage circuit consists of gas discharging tube, pie zore-sistance and clamping diode, with advantages of large discharging capacity, short clamping time and low protection level.
MBX-R/L protector can be mounted on 35mm rail of different standard switching box or distribution box. It does not need screws for connecting with terminal.

Meba power surge MBX-R(L)24

 

Technical Parameter

Arrester MBX-R/L
Mounting position 13
Nominal voltage 5V 6V 12V 24V 48V
Max. continuous operating voltage 7V 9V 15V 30V 51V
Voltage protective level ≤13V ≤20V ≤30V ≤51V ≤100V
Rated loading current of category R 0.2A
Rated loading current of category L 1.0A
Nominal discharging current 10KA
Series connected resistance of each line of category R 15
Series connected inductance of each line of category L 100H
Cross sectional area of connected conductor 0.14-2.5mm2
Peel-off length for the wire to be connected 6-7mm
Color Grey
Material Fire resistant reinforced PC
Applicable standard GB18802.2 IEC61643-21

Outside Size Fig